    HI 504

    pH/ORP Digital Controller with Sensor Check™

    HI 504 is a PID, PI, proportional or on/off pH/ORP controller with one or two set points. The measurement configuration settings and control of pH and ORP are saved separately and permits users to switch between pH and ORP without losing settings. The pH channel can be calibrated in 2 calibration points. The instrument has a full auto diagnostic procedure. Sensor Check™ is also available for pH and ORP probes.

    The temperature is continuously monitored using a temperature sensor (Pt100 or Pt1000 type) with automatic temperature compensation of pH.

    One or two analog controller outputs (0-20 or 4-20 mA) can be configured for pH/ORP recording or controlling (only for models with PID), and relays can be used to control the process or be connected with alarm status.

    Controller status is visable with LED’s on the front panel and on LCD.

    The controllers logging feature can save up to 6000 samples pH/°C or ORP and last 100 error, configuration, calibration and cleaning events. This information can accessible from a PC through RS485 and HI 92500 software. The powerful HI 92500 software has graphing capabilities and can print graphs directly or can be saved as a bitmap. Data can be exported in common spreadsheet formats.

    Sensor Check™ pH/ORP

    Sensor Check™ performs self-diagnostic and troubleshooting functions by continuously verifying the electrode status based on impedance movement of the glass and reference measurement. The internal circuit of the instrument executes two independent tests, one for the probe and one for the reference chamber, measuring the respective impedance values every 5 seconds. These tests last for a very short period to avoid electrolysis and polarization, which can be caused by a prolonged exposure to an electric current. The types of problems identified by Sensor Check™ are: pH electrode broken, reference electrode dirty, reference electrode or matching pin not immersed, clogged or dirty electrode junction, short-circuit between cables of pH and reference electrodes, signal problems from the cable or connector due to humid or dirty environments. The test is not limited to a simple signal that indicates an error in progress, but it reports the nature of the problem with a specific error code.

    Analog Output: Data Logging or PID Dosage Control

    Models are available with one or two analog outputs. These outputs can be connected to a recorder for the catalogging of process data (pH/mV and temperature), or can be used for controlling dosing systems (pumps or electrovalves) using PID control.

    Logging of the Last 100 Events

    With the HI 504 series, it is possible to recall the sequence of the last 100 occurred events at any time: errors, calibrations performed, set parameter changes and cleaning cycles. Every code shown on the display corresponds to a certain type of event, error, or operation.

    Programmable Cleaning Cycles

    Heavy-duty applications often require almost continuous probe maintenance. Elements such as suspended solids, fat, oils, pigments and microorganisms can quickly deposit and soil the glass bulb of a pH probe, the sensor of an ORP probe or the reference junction. To solve these problems, the HI 504 series has been equipped with an automatic cleaning system (simple or advanced, depending on model) with programmable cycles. The cleaning cycle is a simple wash with either water or detergent, programmed by setting the rinse time and the pause length. The advanced cleaning uses both water and detergent, and allows the user to program three stages, with the possibility to vary the sequence, the time, and the number of cycles. The advanced mode can also be triggered at any time from a remote control or through the isolated digital input on the rear panel, which can be connected to an external switch.

    The controllers can also automatically activate both cleaning modes whenever Sensor Check™ reveals a soiled probe. A delay time can be set before restarting the reading after a cleaning cycle has taken place; this allows the probe to adjust to new operating conditions.

    Programmable Hold System

    The hold function allows the user to stop the regulating action of the controller for programmable time periods. It is possible to activate the hold periods in correspondence to programmed operations, such as plant maintenance and cleaning procedures.

    Fail Safe Alarm System

    HANNA’s exclusive Fail Safe Alarm System protects against problems caused by power supply failure or signal interruption, which are typical risks in industrial environments. The system acts both on a hardware and a software level. The alarm relay functions in a normally closed condition, and is tripped when there is a power failure if, for example, the power cable is accidentally cut. This function is very important in industrial plants where alarms are usually not activated if there is a power supply interruption, which can cause serious damage due to a loss of control of the process plant. At the software level, the Fail Safe function activates an alarm in case of abnormal circumstances, for example if the dosing contacts remain closed for an excessive period. The alarm condition is also indicated by a red LED, located directly on the front panel of the controller.

    Specifications

    Range pH -2.00 to 16.00 pH
    ORP -2000 to 2000 mV
    Temperature -30 to 130.0°C
    Resolution pH 0.01 pH
    ORP 1 mV
    Temperature 0.1°C (above -10 °C); 1°C (below -10°C)
    Accuracy @ 20°C pH ±0.02 pH
    ORP ±2 mV
    Temperature ±0.5°C (-9.9 to 130.0°C); ±1°C (-30 to -10°C)
    Input Impedance  1012 Ohm
    Digital Input
    for the pH/ORP/°C
    Transmitter  RS485
    Other Digital
    Insulated Inputs  two digital insulated inputs: one for hold and one for the advanced cleaning; ON state: 5 to 24 VDC
    Digital Insulated
    Output  a digital insulated contact closed upon hold mode
    Temperature
    Compensation  automatic or manual, -30 to 130°C
    Temperature Probe  with three-wire or two-wire Pt100/Pt1000 sensor (with automatic recognition and damage test)
    Power Supply  24 VDC/AC, 115 VAC ±10%, 230 VAC ±10% or 100 VAC ±10%; 50/60 Hz
    Power Consumption  10 VA
    Over Current Protection  400 mA 250V quick blow fuse
    Max. Oscillation
    Frequency  8 MHz
    Relays 1, 2, 3, 4  electromechanical relay SPDT contact outputs, 5A-250 VAC, 5A – 30 VDC (resistive load); fuse protected: 5A, 250V quick blow fuse
    Alarm Relay  electromechanical relay SPDT contact output, 5A – 250 VAC, 5A – 30 VDC (resistive load) fuse protected: 5A, 250V quick blow fuse
    Analog Output  two independent outputs, 0 – 22 mA (configuring as 0-20 mA or 4-20 mA)
    Analog Output
    Resolution  0.1% f.s.
    Analog Output
    Accuracy  ± 2% f.s.
    Data Logging  6000 pH/°C or ORP samples
    Environment  0 to 50°C?(32 to 122°F); RH max 85% non-condensing
    Casing  IP20 (housing); IP54 (front panel)
    Weight  1.6 kg (3.5 lb.)

    Accessories

    Accessories
    HI 92500  Windows® Compatible Software for Micro-processor-based Process Controllers
    Probes
    HI 7610  Stainless Steel Temperature Probe, Pt100 Sensor

     

  • Requesting a Quotation and Ordering Products

    131 Thailand Science Park. Innovation Cluster 1 Building,

    Klong 1, Klong Luang, Pathumthani 12120 Thailand. 

    Tel.  02-191-3928 Fax 02-191-3929


    For more information please contact 081-847-6768 (Ms. Nareerat) IDLine: @alltestkit

    E-mail : info@highents.com

     

    >>Online Quotation Click here<<